Construction Features
- Environmentally Friendly R-404A
- Top Discharge Condenser Exhaust
- Control Panel with Hinged Door
- Insulated Copper Piping
- G-90 Galvanized Cabinet
- Power Terminal Block with Single Point Electrical Connection
- Spring Mounted Compressors Service Valves
| Configuration
- Low Ambient Fan Cycling
- Low Ambient Flooded Condenser Includes Receiver with Isolation Valves (Optional)
- Brazed Plate or Shell and Tube Evaporator
- Condenser Ambient-Fan Cycle Control
- Suction Line Filter-Dryer
- Liquid Line Filter-Dryer
- Thermal Expansion Valve
- Digital Control Thermostat
- Suction and Liquid Vibration Eliminators
- Dual or Single Copeland Discus Compressors
- Cylinder Unloading (Optional)
- Compressor Staging for Dual Compressors (Optional)
- Pump Down Solenoid
Testing
- UL/CL Listed All Models
- Leak Detection, Dielectric and Run Test
|
Refrigerant & Electrical Safety Controls
- Low Water Flow
- Safety Shut-Off
- Short Cycling Time Delay
- Low Refrigerant Pressure Control
- High Refrigerant Pressure Control with Manual Re-Set
- Freeze-Stat with Manual Re-Set
- Temperature Sensor Failure Protection
- Compressor Crankcase Heater
- Control Circuit Fuses
- Sentronic Oil Safety Switch
- Water Inline Strainer
|
Electrical Specifications: DC 25 Ton Refrigeration
*95oF Ambient 2.4 GPM/Ton Entering Water Temperature 55oF, Leaving Water Temperature 45oF.
P/N |
Models |
Volts |
PH |
MCA |
MOPD |
EWT |
Compressor RLA |
Compressor LRA |
BTU* |
App. Wt. |
005498 |
WCDCR2523 |
230 |
3 |
132 |
220 |
54oF |
94 |
470 |
280,100 |
2,300 |
005499 |
WCDCR2543 |
460 |
3 |
66 |
110 |
54oF |
47.2 |
235 |
280,100 |
2,300 |
|
|